1855 - 300 Volt, PVC, Single Pair, Overall Shield, Dekabon™

Description

  • Conductor7-strand bare copper, Class B
  • Primary insulation0.015 inch (0.4 mm) 105C FR-PVC
  • Number of conductors2
  • Color codeBlack and white
  • Pair shield100% coverage, an aluminum-polyester tape shield and a 7-strand tinned copper drain wire
  • Inner jacketBlack FR-PVC
  • Dekabon layerAn aluminum tape 0.008 inch (0.2 mm) thick, coated on both sides with a protective polymer 0.002 inch (0.05 mm) thick
  • Outer jacketDekabon Black CPE

Application

  • Dekabon cable provides special protection against moisture, most chemicals and abrasive backfilling
  • Suitable for direct burial
  • UL listed as PLTC/ITC
  • Suitable for Class I, Division 2 and Class II, Division 2 hazardous areas
  • NEC article 725/727

Bending Radius

  • 12 x d (d = overall diameter)

Cable Type

  • Single pair shielded

Other Options

  • Manufactured in accordance with UL. Also available to ICEA standards or customized configurations.
  • Various metric and AWG size conductors
  • Special color coding of insulation and jacket materials
  • HDPE jacket
  • LDPE jacket

The specifications listed above are subject to change without notice. In any change, the product's performance will remain the same, or be improved.

Electrical Properties Units Conductor Size
20 AWG / 0.5 mm² 16 AWG / 1.3 mm² 1.5 mm²
Resistance [R] Ω/Mft Ω/km 10.5 34.5 4.2 13.7 3.6 11.9
Mutual Capacitance  
Type 1855 pF/ft pF/m 49 160 64 210 67 218
L/R Ratio μH/Ω 9 20 22
Inductance [L] μH/ft μH/m 0.19 0.62 0.17 0.54 0.16 0.53

 

Part Number Pairs Diameter Under Armor Nominal O.D. Weight Jacket Thickness
in mm in mm lb/ft kg/m mils mm
Conductor Size: 20 AWG / 0.5 mm²
1855-086RS 1 0.236 6.0 0.340 8.6 0.070 0.105 35 0.89
Conductor Size: 16 AWG / 1.3 mm²
1855-686RS 1 0.278 7.1 0.384 9.8 0.092 0.137 35 0.89
Conductor Size: 1.5 mm²
1855-N86RS 1 0.286 7.3 0.392 10.0 0.096 0.143 35 0.89