Dekoron Wires and Cables LLC

Products

1863 - 300 Volt, PVC, Single Triad, Overall Shield, Served Wire Armor (SWA)

Description

  • Conductor7-strand bare copper, Class B
  • Primary insulation0.015 inch (0.4 mm) 105C FR-PVC
  • Number of conductors per group3
  • Color codeBlack, white and red
  • Shield100% coverage, an aluminum-polyester tape shield and a 7-strand tinned copper drain wire
  • Inner and outer jacketBlack FR-PVC
  • ArmorMultiple strands of served galvanized steel wire (SWA)

Application

  • UL listed as PLTC/ITC
  • Suitable for Class I, Division 2 and Class II, Division 2 hazardous areas
  • NEC Article 725/727
  • Served wire armor offers cut-through resistance and is suitable for vertical drops
  • 300 volt rated insulation

Bending Radius

  • 12 x d (d = overall diameter)

Cable Type

  • Single triad shielded

Other Options

  • Manufactured in accordance with UL. Also available to ICEA, IEC, BS standards or customized configurations.
  • Various metric and AWG size conductors
  • Special color coding of insulation and jacket materials

The specifications listed above are subject to change without notice. In any change, the product's performance will remain the same, or be improved.

Electrical Properties Units Conductor Size
20 AWG / 0.5 mm² 16 AWG / 1.3 mm² 1.5 mm² 2.5 mm²
Resistance [R] Ω/Mft Ω/km 10.5 34.4 4.1 13.5 3.6 11.8 2.3 7.5
Mutual Capacitance  
Type 1863 pF/ft pF/m 49 161 64 210 67 220 58 190
L/R Ratio μH/Ω 9 20 22 36
Inductance [L] μH/ft μH/m 0.19 0.62 0.17 0.56 0.16 0.52 0.16 0.52

 

Part Number Triads Nominal O.D. Weight Jacket Thickness
in mm lb/ft kg/m mils mm
Conductor Size: 20 AWG / 0.5 mm²
1863-086RR 1 0.347 8.8 0.113 0.168 40 1.02
Conductor Size: 16 AWG / 1.3 mm²
1863-686RR 1 0.394 10.0 0.147 0.219 40 1.02
Conductor Size: 1.5 mm²
1863-N86RR 1 0.413 10.5 0.161 0.240 40 1.02
Conductor Size: 2.5 mm²
1863-P8ARR 1 0.498 12.6 0.250 0.373 40 1.02