Dekoron Wires and Cables LLC

Products

1S60 - 300 Volt, Silicone (Fire Resistant), Single Triad, Unshielded, Unarmored

Description

  • Conductor7-strand tinned copper, Class B
  • Primary insulation0.030 inch (0.8 mm) 90C thermoset silicone alloy
  • Number of conductors per group3
  • Color codeBlack, white and red
  • JacketBlack TPN

Application

  • Provides extended service while exposed to fire
  • Meets IEC 331 and BS 6387 C, S and Z fire tests
  • UL listed as PLTC/ITC
  • Suitable for Class I, Division 2 and Class II, Division 2 hazardous areas
  • NEC Article 725/727
  • 300 volt rated insulation

Bending Radius

  • 6 x d (d = overall diameter)

Cable Type

  • Single triad unshielded

Other Options

  • Manufactured in accordance with UL. Also available to ICEA, IEC, BS standards or customized configurations.
  • Cable constructions to meet BS 6387 C, S, W and Z
  • Various metric and AWG size conductors
  • Special color coding of insulation and jacket materials

The specifications listed above are subject to change without notice. In any change, the product's performance will remain the same, or be improved.

Electrical Properties Units Conductor Size
20 AWG / 0.5 mm² 18 AWG / 0.8 mm² 16 AWG / 1.3 mm² 1.5 mm²
Resistance [R] Ω/Mft Ω/km 11.1 36.4 7.1 23.2 4.4 14.5 3.8 12.4
Mutual Capacitance  
Type 1S60 pF/ft pF/m 16 54 18 58 19 63 20 65
L/R Ratio μH/Ω 10 14 21 25
Inductance [L] μH/ft μH/m 0.22 0.72 0.2 0.67 0.19 0.62 0.19 0.61

 

Part Number Triads Nominal O.D. Weight Jacket Thickness
in mm lb/ft kg/m mils mm
Conductor Size: 20 AWG / 0.5 mm²
1S60-08603 1 0.310 7.9 0.056 0.084 40 1.02
Conductor Size: 18 AWG / 0.8 mm²
1S60-88603 1 0.331 8.4 0.066 0.099 40 1.02
Conductor Size: 16 AWG / 1.3 mm²
1S60-68603 1 0.339 8.6 0.075 0.111 40 1.02
Conductor Size: 1.5 mm²
1S60-N8603 1 0.350 8.9 0.080 0.119 40 1.02