2X52 - 600 Volt, XLPE, Single Pair, Overall Shield, Unarmored
Description
- Conductor7-strand bare copper, Class B
- Primary insulation0.030 inch (0.8 mm) XLPE
- Color codeBlack and white
- Group identificationEach pair numbered
- Pair shield100% coverage, an aluminum-polyester tape shield and a 7-strand tinned copper drain wire
- JacketBlack FR-PVC
Application
- UL listed TC
- Excellent dielectric properties
- Good chemical and long-term moisture resistance
- NEC Article 336
- Flame retardant
- 600 volt rated insulation
Bending Radius
- 6 x d (d = overall diameter)
Cable Type
- Single pair shielded
Other Options
- Manufactured in accordance with UL. Also available to ICEA, IEC, CSA, BS standards or customized configurations.
- Various metric and AWG size conductors
- Special color coding of insulation and jacket materials
- CPE or Hypalon (CSPE) jacket
The specifications listed above are subject to change without notice. In any change, the product's performance will remain the same, or be improved.
Electrical Properties | Units | Conductor Size | |||||||||
16 AWG / 1.3 mm² | 14 AWG / 2.1 mm² | 1.5 mm² | 2.5 mm² | ||||||||
Resistance [R] | Ω/Mft | Ω/km | 4.4 | 14.5 | 3.8 | 12.4 | 2.7 | 8.8 | 2.3 | 7.5 | |
Mutual Capacitance | |||||||||||
Type 2X52 | pF/ft | pF/m | 29 | 96 | 30 | 99 | 33 | 109 | 35 | 115 | |
L/R Ratio | μH/Ω | 23 | 26 | 34 | 40 | ||||||
Inductance [L] | μH/ft | μH/m | 0.2 | 0.66 | 0.2 | 0.64 | 0.18 | 0.61 | 0.18 | 0.6 |
Part Number | Pairs | Nominal O.D. | Weight | Jacket Thickness | ||||||
in | mm | lb/ft | kg/m | mils | mm | |||||
Conductor Size: 16 AWG / 1.3 mm² | ||||||||||
2X52-69610 | 1 | 0.334 | 8.5 | 0.063 | 0.094 | 45 | 1.14 | |||
Conductor Size: 14 AWG/ 2.1 mm² | ||||||||||
2X52-49610 | 1 | 0.364 | 9.2 | 0.080 | 0.119 | 45 | 1.14 | |||
Conductor Size: 1.5 mm² | ||||||||||
2X52-N9610 | 1 | 0.342 | 8.7 | 0.067 | 0.099 | 45 | 1.14 | |||
Conductor Size: 2.5 mm² | ||||||||||
2X52-P9610 | 1 | 0.378 | 9.6 | 0.088 | 0.130 | 45 | 1.14 |